Telecom shelters, pump stations, and remote equipment buildings may only see a technician a few times a year. Wall mount units are built for that kind of duty, but a short checklist on every visit prevents most failures.
Every visit
- Filters. Replace them. A clogged filter is the most common cause of low airflow, frozen coils, and high-temperature alarms. Dusty sites may need more frequent changes.
- Condenser coil. Look for dirt, cottonwood, grass clippings, and debris. Clean as needed. A dirty condenser coil drives up head pressure and power use.
- Clearances. Make sure nothing new is blocking airflow, such as stored equipment, weeds, or snow drifts.
- Alarms and controls. Check the controller for logged alarms and confirm the lead/lag rotation is working.
- Listen. Unusual fan or compressor noise is often the first sign of a problem.
At least once a year
- Check electrical connections for tightness and signs of heat.
- Check contactors and capacitors.
- Measure amp draw and compare it to the nameplate.
- Check the condensate drain and make sure it flows freely.
- Check cabinet gaskets and the wall seal for gaps where outside air, water, or pests could get in.
Economizer units
- Cycle the dampers and confirm they open and close fully.
- Check the outside-air sensor and the economizer changeover setting.
- Make sure damper blades and linkages are clean and move freely.
Keep a log
Record the date, what was checked, filter changes, and any readings. A log makes warranty claims easier and helps spot a unit that's starting to decline.